Disturbance and fault records

Stedin’s protection relays (inferred as SIPROTEC 5 and SEL-451, not independently confirmed) record disturbance data: high-fidelity waveforms captured at the instant a protection event is detected. These recordings, stored in COMTRADE format (IEEE C37.111 / IEC 60255-24), are the highest-confidence forensic evidence available for understanding what the relay actually measured and why it operated.

COMTRADE format and contents

COMTRADE (Common Format for Transient Data Exchange) is a standardised binary format for recording waveform data from power-system equipment. A COMTRADE file contains: the sampled values of currents, voltages, and status signals at high frequency (typically 256 or 1024 samples per second or higher), the timestamp of when sampling started, and the configuration data specifying what signals were recorded and their scaling factors.

When a relay detects a fault condition, it initiates a disturbance recording. The sampling had typically been running continuously or on demand, and when the fault is detected, the relay captures the waveforms surrounding the fault: typically a pre-fault window (seconds before the fault is detected), the fault window (seconds during which the fault persists), and a post-fault window (seconds after the fault is cleared). The relay stores the recording in its memory, and the recording is later extracted via engineering tools or via a gateway connected to the relay.

A COMTRADE file is the most objective evidence available because it is a hardware-level capture. The relay’s analogue-to-digital converter sampled the actual voltage and current waveforms from sensors (current transformers, potential transformers, analogue circuits). The digital recording reflects what the hardware measured, not what any software deduced. Falsifying a COMTRADE file would require either: modifying the hardware’s measurement at the instant the waveform was recorded (impossible, the hardware samples what is present), or forging the COMTRADE file after the fact (which would require detailed knowledge of the waveform format and the discipline to keep every altered sample internally consistent with the physics of the event).

COMTRADE interpretation and physical validity

A COMTRADE file is interpreted by plotting the sampled waveforms and inspecting them for the signatures of faults. An overcurrent fault appears as a sudden increase in current. An overvoltage fault appears as a sudden increase in voltage. An underfrequency condition appears as the frequency calculated from the voltage waveform (by counting zero-crossings) dropping below the nominal 50 Hz.

For a legitimate fault, the waveforms show clear physical signatures. An overcurrent fault shows current amplitude increasing suddenly, and in three-phase systems, the three current phases may show an imbalance (depending on the fault type: line-to-line, line-to-ground, etc.). The transient is visible: a sudden jump from the pre-fault steady-state to the fault condition. After protection operates (after the relay’s trip signal opens a breaker), the current drops back toward normal (or to zero if the faulted section is fully isolated).

Anomalous or unphysical waveforms in a COMTRADE file are red flags. A COMTRADE showing perfectly sine-wave voltage and current with no noise is suspicious (real power systems have continuous variation and noise). A COMTRADE showing a fault condition that appears to violate physical laws (current flowing backward when it should flow forward, or unbalanced three-phase currents that sum to a non-zero value when they should sum to zero) indicates either sensor malfunction or forged data.

COMTRADE file integrity

COMTRADE carries little integrity protection of its own. The original editions define no checksum at all, and the 2013 edition added only an optional CRC that covers the ASCII configuration file, not the binary waveform samples. Most records in the field carry no checksum, so a clean-looking file proves nothing about whether the waveform was altered.

Integrity rests elsewhere. A forged COMTRADE has to keep every altered sample internally consistent, across the pre-fault, fault and post-fault windows and across all three phases, with the physics of the event it claims to record. That is difficult to do convincingly by hand. The stronger check is external: the waveform is compared against independent measurements of the same event (the RTU’s readings, the historian’s stored values, a second relay’s capture). A relay whose firmware has been modified to emit synthetic waveforms defeats any file-level check, because the false data is generated at source. Only physical-plausibility analysis and cross-source comparison catch that case.

Cross-checking COMTRADE against other measurement sources

The power-system measurements in a COMTRADE file are consistent with other independent measurement sources when nothing has gone wrong. A SIPROTEC relay that recorded a COMTRADE showing an overcurrent fault at a location has, as its corroboration, the RTU at that location reading increased current at approximately the same time and the historian holding the same measurements. The three independent sources agree.

If the COMTRADE shows a fault at 10:00:00.000 UTC with a measured current of 1500A, the RTU’s log carries high current at approximately 10:00:00 UTC (clock drift stays small with NTP synchronisation) and the historian the same current at that time. The three sources align.

A divergence is forensic evidence of tampering or malfunction. If the COMTRADE shows a fault at 10:00:00 UTC but the historian shows normal current at 10:00:00 UTC and high current at 10:05:00 UTC, either the COMTRADE’s timestamp is wrong, or the historian’s measurements are wrong, or one of the systems is falsifying data. The investigation would proceed by examining clocks, NTP synchronisation, and other evidence to determine which source is trustworthy.

Relay event log and COMTRADE correlation

A relay’s event log (separate from the COMTRADE) records when faults are detected and when protection operates, with timestamps. The event log carries an entry for a fault detection at the instant the COMTRADE begins recording the fault, and the event log timestamp matches the COMTRADE’s start timestamp (allowing for clock synchronisation differences).

If the event log shows a relay trip at 10:00:10 UTC but the COMTRADE shows the fault beginning at 10:00:05 UTC, the timing divergence requires explanation. Possible explanations include: the relay’s clock drifted by 5 seconds (clock synchronisation issue), or the COMTRADE was misdated (timestamped incorrectly), or the event log is incomplete (the relay detected and began recording the fault 5 seconds before it officially recorded the trip event).

Missing COMTRADE files

If a relay’s event log shows it detected a fault and tripped, a COMTRADE file recording that event is normally stored on the relay. If the COMTRADE file is not found (either the relay’s memory is full and old COMTRADE files were overwritten, or the file is missing for another reason), that is forensically significant.

A missing COMTRADE for a significant event is hard to explain innocently. A relay that claims to have detected and responded to a major fault, but has no COMTRADE recording of that fault, is missing the hardware record a real trip would leave. The COMTRADE would normally be automatically generated; its absence suggests either the relay was operating in a mode where COMTRADE recording was disabled, or the COMTRADE was deliberately deleted, or the fault-detection event was recorded but the actual fault did not occur (the event log was falsified).

Disturbance playback and simulation

Some SCADA systems can play back COMTRADE files to understand how a relay would have responded to a historical fault. This capability is useful for forensic analysis: if a COMTRADE from a fault is available, the relay can be taken offline and the COMTRADE can be played back through a relay simulator to verify that the relay would indeed respond as it did during the actual event.

If the replay shows the relay would not have responded as documented (for example, the replay shows the relay’s threshold was not exceeded, but the relay’s event log shows it tripped), then either the COMTRADE is not representative of the actual fault, or the relay’s settings were different during the actual event than they are now, or the event log is falsified.

This testing method provides independent validation of a relay’s response. If the relay is suspected of having been compromised (settings changed, firmware modified), the relay testing provides evidence of the compromise. A relay that would not trip to a known fault condition is not functioning as configured.

Fault sequences and protection coordination

When multiple relays protect the same fault point (primary protection and backup protection), their COMTRADE files show the same fault sequence, with similar measured values (current, voltage), and with the primary relay responding before the backup relay (if protection coordination is working correctly).

If the primary relay’s COMTRADE shows a fault at 10:00:00 UTC and the relay tripped immediately, the backup relay shows the same fault at 10:00:00 UTC. If the backup relay’s COMTRADE shows the fault at 10:00:05 UTC (5 seconds later), the timing divergence indicates either clock skew, or one of the relays is measuring at a different location and is seeing a delayed version of the fault propagation, or one of the COMTRADE files is unreliable.

Proper protection coordination is verified by examining the COMTRADE files: the primary relay detects and responds, the backup relay detects the same fault but does not trip (because the primary relay already cleared it). The COMTRADE files document this sequence and allow auditors to verify that the protection system operated as designed.

Evidence of relay malfunction versus compromise

A relay’s COMTRADE files can distinguish between malfunction and compromise. A malfunctioning relay might produce erratic COMTRADE files (garbled data, inconsistent timestamps, impossible waveforms), indicating a hardware or software bug. A compromised relay may instead produce normal COMTRADE files that correctly record real faults (because the compromise is selective: only under specific conditions does the relay misbehave), or emit false COMTRADE files (if the attacker modified the firmware to generate synthetic waveforms).

Systematic analysis of COMTRADE files over time can reveal patterns. If all COMTRADE files from a relay are suspicious ( implausibly smooth waveforms, no noise, physically implausible), the relay is likely compromised or malfunctioning. If most COMTRADE files appear normal but a few are anomalous (corresponding to the times when unauthorised work is suspected to have occurred), the relay may have been conditionally compromised (malicious code activated only under specific conditions).