Metre data semantics¶
Stedin’s smart-meter base (Landis+Gyr, Iskraemeco, Kaifa, Sagemcom) reports consumption data via CDMA to the metering platform. The meters record cumulative kilowatt-hours consumed, and the platform aggregates readings across customers, feeders, and the entire network. Consumption patterns, anomalies, and the relationship between meter readings and network measurements form the observable layer for metering integrity.
Normal consumption patterns and baselines¶
The meters record consumption continuously. A residential meter in a typical Dutch home consumes 8-15 kWh per day in winter (heating load) and 3-8 kWh per day in summer. An office building shows a sharp daytime peak (08:00-18:00) and minimal nighttime consumption. A supermarket shows steady baseline load (refrigeration, lighting) plus daily peaks around shopping hours. Industrial customers show load that correlates with production schedules. These patterns are consistent and repeatable year-over-year, with seasonal variation and day-of-week variation (weekday loads differ from weekend loads).
Stedin’s metering platform aggregates readings at multiple levels: individual meter, district, feeder, substation, and network-wide. The aggregated consumption shows the sum of all customer consumption downstream of a measurement point. A feeder’s total consumption at 15:00 matches the sum of all meter readings downstream of that feeder. When consumption is compared across aggregation levels, the pyramid balances: the sum of all customers equals the sum of all meters, which equals the sum of all feeders, which equals the network-wide total.
The baseline for each meter, district, feeder, and substation is constructed from historical data. The expected consumption pattern for a Tuesday afternoon in March is known with reasonable precision. When real-time data arrives, it is compared against the baseline. A meter that normally shows 2 kW steady load suddenly dropping to zero is anomalous. A feeder that normally shows 50 MW at midday suddenly showing 30 MW stands out. A network-wide consumption that diverges from the expected pattern by more than a few per cent points the same way. These anomalies can indicate equipment failure, customer usage change, meter malfunction, or tampering.
Meter-to-network measurement alignment¶
Stedin’s distribution network has multiple independent measurement sources. Smart meters measure consumption at individual customer points, aggregating to feeders and substations. RTUs at substations measure total feeder consumption via CT (current transformer) inputs and report to the SCADA and historian. These two independent measurement sources ( meters and RTUs) show alignment. The sum of all meter readings on a feeder approximately equals the RTU’s measurement of total feeder consumption at the feeder’s source point.
When meter readings and RTU measurements diverge, the divergence is a forensic signature. If individual meters report 500 kWh consumed on a feeder but the RTU reports 600 kWh flowed into that feeder from the source, there is a gap (100 kWh of energy unaccounted for). The gap could indicate: a meter is under-reporting (a tampered or malfunctioning meter is not recording all consumption), energy theft (a customer bypassing their meter), a non-metered customer consuming energy, or the RTU’s measurement is wrong. Conversely, if meters report 600 kWh but the RTU reports 500 kWh, the meters are over-reporting or the RTU’s measurement is wrong.
Normal alignment is within a few per cent (the difference between what meters report and what RTUs measure for the same feeder is typically less than 3-5 per cent, accounting for technical losses in the network and metering uncertainty). Larger divergences require investigation. A feeder where meters consistently report 10 per cent more consumption than the RTU measures is suspicious and could indicate systematic meter over-reporting or RTU under-reporting. A specific customer whose meter reports 20 per cent more consumption than their RTU-measured usage would suggest is anomalous.
Consumption profile anomalies¶
Individual customer consumption profiles develop over time and become predictable. A residential customer’s profile shows morning and evening peaks, a daytime trough, and very low nighttime consumption. If that customer’s profile suddenly flattens (no daily variation, steady constant consumption throughout the day and night), that is anomalous. The anomaly could indicate the meter is falsifying data, or the customer’s actual usage changed dramatically.
Geographic patterns also appear. All meters on a specific feeder show seasonal variation that tracks the external temperature (higher consumption in winter, lower in summer). If one feeder suddenly shows inverted seasonality (highest consumption in summer), that feeder’s meters are anomalous. If all feeders in a specific district show suspicious round numbers (all customers reporting exactly 1000 Wh consumed, with no variation), that is evidence of synthetic data.
Consumption anomalies that correlate with events are informative. If a feeder’s total consumption suddenly drops by 50 per cent at a specific instant, that could indicate: a large customer disconnected, a protection relay tripped the feeder off (which would be visible in SCADA logs), energy theft was suddenly removed, or the meters are falsifying data. Comparing the consumption drop against the SCADA event log shows whether a relay trip explains the drop. If there is no relay trip and no disconnection in SCADA logs, the drop is unexplained.
Meter tampering signatures¶
Meter tampering can take several forms, each with distinct signatures. A meter can be physically bypassed (a circuit shunt or reverse-polarity connection is installed so the meter does not record the consumed energy). The visible signature is that the meter’s consumption does not match the customer’s actual load (which can be estimated from other sources like billing complaints or electricity-company inspection) or the meter reading stays constant when the customer reports consuming power.
A meter can be remotely modified if it accepts remote commands via CDMA. The signature of remote tampering is that the meter’s consumption value suddenly resets or jumps without a corresponding disconnection-reconnection event. A meter reading that goes backward (consumption decreases instead of increasing) is an obvious signature, as meters are designed to record cumulative consumption only.
A meter can be swapped. A tampered or non-reporting meter is physically replaced with a different meter that reports artificially low consumption. The signature is a discontinuity in the meter’s serial number or an abrupt change in the consumption profile at the instant of meter replacement. If a meter ID suddenly changes and the consumption history resets, that indicates a meter replacement. The question is whether the replacement was documented (a work order authorises the replacement) or unauthorised.
A meter’s reported consumption can be altered during transmission or at the platform. If the meter correctly records and reports 1000 Wh, but the metering platform receives 500 Wh, the data was modified in transit or at the platform. The signature is a divergence between what the meter transmitted (visible in Utility Connect’s CDMA logs if available) and what the platform recorded. If the platform’s audit log shows the value was edited (who edited it, when, what the old value was), that is the signature of manual tampering.
Non-technical losses and energy theft¶
Stedin recognises several classes of electricity loss. Technical losses are expected: electricity dissipates as heat in the distribution network’s conductors, transformers have inherent losses, and metering has inherent uncertainty. Non-technical losses are energy that is consumed but not properly metered or billed, including energy theft, metering errors, and unauthorised connections.
Non-technical losses are estimated as the gap between the total energy input to a region (measured by the wholesale market) and the total metered consumption (sum of all meter readings). When non-technical losses spike above the expected baseline, investigation is warranted. A district that normally shows 2 per cent loss suddenly showing 8 per cent loss indicates either a new systematic metering problem, energy theft, or new unauthorised load.
Individual meters or customers can also be outliers. If a specific customer shows a consumption that is substantially lower than their historical average and lower than structurally similar customers in the same area, they may be bypassing their meter. If a customer shows zero consumption (a meter reading that does not change) despite active load visible at the property (electrical service lines present, customer still occupied), the meter is likely tampered. Identifying such outliers requires statistical analysis, but the signatures are clear when found.
Regulatory and billing applications¶
Stedin’s metering data flows to Netbeheer Nederland for the national energy balance and to billing systems for customer accounts. The data also flows to regulators who verify that metering is accurate. When metering data is disputed (a customer claims they were over-billed, or a regulator questions Stedin’s reported network losses), the meter readings are the source of evidence.
Stedin has been involved in metering disputes with the ACM (Dutch energy regulator). In one dispute over meter readings, it was Stedin’s own logbook, the physical record of repeated in-person attempts to read a meter, that proved decisive: the ACM accepted it as evidence that Stedin had met its reading obligation and ruled the complaint unfounded. The handwritten record carried the point the digital platform alone could not.
The metering platform’s audit logs (who accessed the data, when, and what changes were made) are forensic sources for understanding whether data was modified. If the audit log shows that a technician accessed meter XYZ’s record and manually edited the consumption value from 1000 Wh to 800 Wh without a corresponding technical reason, that is evidence of tampering. Conversely, if the audit log is complete and shows no such edits, the data is more trustworthy.
Consumption forecasting and anomaly detection¶
Stedin’s metering platform can apply statistical models to detect anomalies. A model predicts the expected consumption for each customer based on historical data, weather, calendar (weekday/weekend), and seasonal factors. When real-time meter readings arrive, they are compared against the prediction. Readings that deviate significantly from the prediction are flagged for investigation.
This approach is effective for detecting sudden changes (a meter that stops reporting due to malfunction, or a customer who suddenly increases consumption due to new equipment). It is less effective for detecting gradual systematic tampering (a meter that slowly under-reports by 1 per cent per day). The strength of anomaly detection is that it is automated and scalable (thousands of customers can be monitored continuously). The limitation is that it generates false positives (legitimate consumption changes trigger alerts) and requires human review to distinguish legitimate anomalies from tampering.
For forensic analysis, anomaly detection can provide initial leads. If a district shows unusually high consumption that does not match expectations, that is a pointer to investigate. If anomalies cluster geographically (all meters in one substation district are anomalous), that suggests a systematic problem at that location. If anomalies correlate temporally (all anomalies occur at night or all occur on weekends), that suggests a pattern related to behavioural or operational factors.