Configuration attacks¶
Threats that work by changing system configuration: modifying SCADA settings, altering protection relay thresholds, changing engineering parameters, corrupting the network model, or altering alarm thresholds to cause false operations or mask events.
Configuration attacks leave traces in the engineering tools, version control, settings databases, and the comparison between what should be running and what actually is.
SCADA configuration manipulation¶
Stedin’s SCADA system (e-terracontrol suite: e-terracontrol for SCADA/EMS and e-terra distribution for DMS) maintains settings that govern how commands propagate to field devices, how alarms are generated, and how the system responds to abnormal conditions. These settings include device addresses, communication parameters, alarm thresholds, and control logic. If an attacker can modify these settings, they can change how e-terracontrol operates without modifying the underlying control room interface.
An attacker with access to the engineering environment could modify configuration before deployment. The changes look innocuous: add a parameter, change a timeout, adjust a constant. But if designed to interact with specific field conditions, they cause unexpected behaviour. If the attacker changes the load-shedding logic during frequency deviation, e-terracontrol sheds load too aggressively or not at all. Changing the communication retry timeout makes the system abandon device attempts too quickly, leaving commands unacknowledged.
CONFIGURATION ATTACK SURFACE: Three compromise stages
─────────────────────────────────────────────────────
STAGE 1: Engineering Workstation
┌─────────────────────────────────────────┐
│ DIGSI 5 / AcSELerator / e-terracontrol │
│ configuration editor │
└─────────────────────────────────────────┘
│
COMPROMISE POINTS:
• Malware on workstation (supply-chain, phishing)
• Credential theft (engineer account compromised)
• Physical access (install USB device, keylogger)
EVIDENCE LEFT:
• Settings files modified (timestamp, version history)
• Editing tool session logs (who, when, what changed)
• Workstation event logs (unusual process execution)
STAGE 2: Build/Test/Deployment Pipeline
┌─────────────────────────────────────────┐
│ Configuration packaged │
│ Testing in lab environment │
│ Reviewed for correctness │
│ Ready for deployment │
└─────────────────────────────────────────┘
│
COMPROMISE POINTS:
• Intercept config during transfer (network compromise)
• Compromise test environment (make fake tests pass)
• Forge approval/review signatures
• Supply-chain compromise (vendor delivery)
EVIDENCE LEFT:
• File checksums mismatch (config differs from signed version)
• Test logs show tampering (impossible test results)
• Build logs missing/altered (who touched the package)
• Configuration file timestamps inconsistent
STAGE 3: Live System Deployment
┌─────────────────────────────────────────┐
│ e-terracontrol running in production │
│ Configuration active on live system │
│ Changes affect real network behaviour │
└─────────────────────────────────────────┘
│
COMPROMISE POINTS:
• Direct database access (database credentials)
• Network access to e-terracontrol (API, RPC)
• Supply-chain (compromised patch/update)
• Insider with system access
EVIDENCE LEFT:
• Configuration divergence (baseline vs actual)
• Change logs (who logged in, what changed, when)
• Operator observations (unexpected system behaviour)
• Audit trail gaps (missing entries during timeframe)
ATTACKER'S DILEMMA at each stage:
─────────────────────────────────
Stage 1: Changes are obvious (file timestamps, settings diffs)
→ Must hide in legitimate maintenance window
Stage 2: Testing is supposed to catch problems
→ Must either compromise tests or smuggle past them
Stage 3: Live system has baselines and monitoring
→ Configuration comparison immediately flags divergence
→ Must either modify baselines OR activate only under
specific trigger conditions (avoid detection)
The deployment of new e-terracontrol configuration follows Stedin’s change-control process: the configuration is built and tested in a lab environment, reviewed for correctness, and then deployed to the live system during a maintenance window. This process is auditable, but an attacker could compromise it at any stage. They could compromise the engineering workstation before the configuration is built, modify the configuration after it is built but before deployment, or modify the live system’s configuration after deployment. Each approach leaves different evidence trails. Detecting unauthorised modifications turns on Stedin’s change cadence and approval processes: when and how changes are authorised, who performs them, and what documentation trails they leave.
Protection relay settings compromise¶
Stedin’s protection relays (inferred as SIPROTEC 5 or SEL families like SEL-451, not independently confirmed) are configured through engineering tools (DIGSI 5 for SIPROTEC, AcSELerator QuickSet for SEL). A relay’s protection settings define when the relay will trip (and thus isolate a fault), and how quickly. These are safety-critical settings: if they are set incorrectly, the relay might trip when it should not (nuisance trip) or might not trip when it should (leaving a fault uncontrolled and allowing it to spread).
An attacker who can modify the relay settings would target specific thresholds. For instance, changing an overcurrent threshold from 1200A to 1500A would cause the relay to tolerate larger fault currents before tripping. Changing a time delay from 100 milliseconds to 500 milliseconds would delay the trip, allowing the fault to persist longer. Disabling a protection function entirely (like disabling ground-fault detection) would leave a class of faults unprotected. Each of these changes can be made through DIGSI 5 or AcSELerator QuickSet if the attacker has access to them.
Settings are managed through a baseline configuration that is stored in the relay’s non-volatile memory and also in the engineering tool database. When a technician connects to a relay to perform maintenance, they can compare the current settings against the baseline by connecting DIGSI 5 or AcSELerator QuickSet and performing a “Read Settings” operation. This online-versus-offline comparison is a standard diagnostic step and serves as an integrity check. An attacker trying to hide a relay settings change would need to modify not only the settings on the relay device itself but also the baseline settings stored in the tool database, so that the comparison returns a match even though the relay is running non-standard settings.
Relay settings are also logged in the relay’s own event records. The relay records when settings were changed, who changed them (if the relay has an audit capability), and when the change was implemented. These logs are visible through the relay’s user interface and are collected in the historian. An attacker could modify these logs to hide evidence of a settings change, but doing so requires either physical access to the relay’s memory or network access to the relay with sufficient privilege to edit the relay’s event database.
Engineering tool abuse¶
The engineering tools used to configure relays (DIGSI 5 for SIPROTEC, AcSELerator QuickSet for SEL), Stedin’s SCADA system (e-terracontrol), and the network model (Smallworld with Lovion integration) typically run on restricted workstations that are not connected to the public internet but may be connected to the internal network. These tools often run with administrative or elevated privileges, because they need to write settings to device memory and modify system configurations.
An attacker who compromises an engineering workstation could launch attacks through the tools. If DIGSI 5 is running on a workstation and is connected to a relay, the attacker could use DIGSI 5 to modify relay settings. If e-terracontrol is running and is connected to the SCADA network, the attacker could modify SCADA configuration. The tools themselves are installed from vendor software packages and are updated through vendor patches. If a vendor package is compromised (either at the source or during download), or if a patch contains malicious code, the attacker could gain access to the engineering environment and thus to the systems the tools manage.
Who has access to these tools is a key part of understanding the attack surface. Stedin’s own engineers have access, and contractors performing relay maintenance and configuration work also have access during maintenance windows, under how Stedin vets and grants access to contractors and when that access is authorised.
Stedin’s change-control process typically requires that all configuration changes be made by authorised personnel following documented procedures. An engineering tool might log who connected, when, what settings were accessed, and whether changes were made. But if the attacker is using a legitimate tool that is authorised to make changes, and the attacker has stolen credentials or is impersonating a technician, the audit trail will show a legitimate user making a change.
Network model corruption¶
Stedin’s network model (maintained in Smallworld GIS with Lovion integration for network documentation) is the single source of truth for the network’s topology: what substations exist, what feeds into what, what the voltage levels are, what switching points are available, and what protection zones exist. This model feeds into e-terracontrol SCADA, which uses it to determine which field devices to communicate with, which commands are safe to execute, and what feedback to expect.
An attacker who can modify the network model could cause e-terracontrol to send commands to the wrong devices. For instance, if a switchpoint is defined in the model as “Substation A, Feeder 1” but is actually located at “Substation B, Feeder 3”, and the model is corrupted to swap these definitions, then an operator intending to isolate a fault at Substation B would actually isolate it at Substation A. The operator would see in their e-terracontrol display that the intended load has been shed, and would have no way to know that the wrong load was actually shed.
More subtly, an attacker could modify the network model to add phantom devices or remove real ones. A phantom device would be sent commands by e-terracontrol and the operator would see confirmation messages, but nothing would actually happen at the field. A removed device would be sent commands that would fail to execute, and the operator would see a communication error. Over time, if many devices are removed from the model, the operator’s view of the network becomes increasingly inaccurate, and their ability to make safe decisions degrades.
The network model is maintained in a centralised database (Smallworld on-premises or cloud-based) and is updated through documented change processes. Changes to the model are typically made by Stedin’s GIS engineers and require the approval of the network-engineering function. But if access to Smallworld is compromised (through credential theft or through a supply-chain compromise of the Smallworld software itself), changes could be made without going through the normal approval process.
Alarm threshold manipulation¶
Stedin’s e-terracontrol SCADA system is configured to generate alarms when certain conditions occur: frequency deviations, voltage violations, communications failures, temperature alarms at power equipment. These alarms are visual and sometimes audible, and trigger operator attention. Alarms are also logged in Stedin’s event journal and are used by analytics tools to detect emerging faults.
An attacker who can modify alarm thresholds in e-terracontrol could cause alarms to not trigger when they should (making a fault appear normal), or to trigger too often (causing alarm fatigue, where operators learn to ignore alarms and might miss a real fault). For instance, changing a voltage-alarm threshold from 0.9 per-unit to 0.8 per-unit would prevent an alarm from triggering during a sustained under-voltage event that is genuinely hazardous but just barely stays above the new threshold. Alternatively, changing a communication-timeout alarm to trigger extremely frequently could cause so many false alarms that operators might disable the alarm entirely rather than deal with the noise.
Alarm configuration is typically stored in e-terracontrol’s configuration database and is deployed to the live system during maintenance windows. Because alarms are user-visible, changes to alarm thresholds are often more noticeable than changes to internal control logic. An operator who is watching the e-terracontrol display and sees an alarm suddenly appear or disappear might investigate whether the system has changed. But if the alarm threshold is changed gradually over multiple updates, or if the change coincides with a legitimate system update, it might not be noticed.
Settings baseline divergence¶
Stedin maintains a baseline of all system settings: SIPROTEC and SEL relay protection settings, e-terracontrol SCADA configuration, Smallworld network model, alarm thresholds, device communication parameters. When maintenance is performed on any system, the settings that change are documented and approved. After the maintenance window, the system’s settings should match the updated baseline.
An attacker who introduces unauthorised configuration changes faces the risk that those changes will be discovered during a routine baseline comparison at Stedin. If an operator periodically connects to each relay and performs a Read Settings operation through DIGSI 5 or AcSELerator QuickSet, comparing the current settings to the baseline, a divergence will be flagged. Similarly, if an operator periodically exports the e-terracontrol configuration and compares it against a known-good version, changes will be visible. How these baselines are established, maintained, and tested is foundational to understanding what unauthorised changes would appear as, and follows how Stedin verifies and documents baseline settings.
The time interval between baseline comparisons is the blind spot. If the operator compares settings annually, an attacker has a year to exploit the changes before they are discovered. If comparisons happen monthly, the window is smaller. If comparisons happen continuously through an automated integrity-checking tool, the window is minimal. But continuous integrity checking requires that the checking tool itself is trustworthy and that the baseline it is comparing against is accurate. An attacker who compromises both the live system and the baseline database could maintain the illusion of consistency while running unauthorised settings on the live system.
Evidence of configuration changes can be found in several places: the relay’s own event log (which records settings changes), e-terracontrol’s transaction log, the engineering tool’s connection logs (showing when DIGSI 5 or AcSELerator QuickSet connected to a device), and IBM Maximo’s audit trail (which records changes to asset records and maintenance activities). The challenge is that legitimate maintenance generates the same kinds of records: Stedin engineers connecting to relays, systems being modified, and settings being updated. Distinguishing between an authorised change and an unauthorised one requires understanding what the change was, whether it was approved, and whether it matches the documented maintenance activity for that time period.