Maintenance window abuse

Threats that exploit planned maintenance windows: using a legitimate maintenance period as cover for unauthorised work, hiding unauthorised changes within scheduled changes, or abusing the reduced oversight that maintenance windows provide.

Maintenance windows follow a published schedule, are announced to customers and operators in advance, and follow documented procedures. During maintenance, work is authorised through work plans and switching plans that define what will be done. Abuse of a maintenance window means either unauthorised work executed during it, or authorised work that includes hidden unauthorised changes.

The distinction between legitimate and unauthorised work depends on the work plan, the switching plan, the record of what was actually done, and whether the results match the authorisation.

Unauthorised work during scheduled maintenance

Maintenance windows at Stedin are announced well in advance and are coordinated through the Bedrijfsvoering application. A werkplan (work plan) defines what work will be done, a bedieningsplan (switching plan) defines what switching operations are required to isolate the work area safely, and a work order in IBM Maximo tracks the maintenance activity and its completion. What windows are legitimate follows Stedin’s maintenance announcement rhythms, procurement schedules, and the change cadence that gates work.

A maintenance window creates a window of legitimacy: the network is expected to be in an altered state, equipment is expected to be de-energised or energised in ways that would otherwise be unusual, and personnel are expected to be on site in the maintenance area. An attacker with access to this window could execute unauthorised work alongside or instead of the authorised work.

For instance, a scheduled maintenance activity at Stedin might require opening a switchpoint to isolate a section of network for equipment maintenance. During this window, the attacker could additionally reprogram an RTU in the same substation, steal components, or plant monitoring equipment. The unauthorised work would occur within the scope of the maintenance window, and the attacker could rely on the reduced oversight during maintenance to avoid detection.

An insider (a Stedin contractor or employee) with access to the maintenance window is particularly dangerous, because they understand the work procedures and can blend in with legitimate maintenance activities. They can claim to be part of the maintenance team, access equipment and systems during the window, and perform unauthorised actions. Contractors make up roughly 18 per cent of Stedin’s workforce and perform much of the field maintenance, working under how contractors are vetted and authorised within a workforce structure whose thinness affects oversight. An external attacker would need to either impersonate Stedin maintenance personnel (which requires knowledge of the procedures and access to the site) or coordinate with an inside accomplice.

Stedin’s werkplan and bedieningsplan are documented in advance, so an attacker can study them before the maintenance window to understand what will be happening and where attention will be focused. This allows pre-planning of the unauthorised work.

MAINTENANCE WINDOW TIMELINE: Opportunity for Unauthorised Work
──────────────────────────────────────────────────────────────

ADVANCE PLANNING PHASE (days before)
────────────────────────────────────

T-7 days: Werkplan published
  • Stedin publishes maintenance schedule to customer portal
  • Attacker (insider or external with access) studies it
  • Identifies target: "Switchpoint replacement at Substation X, 15:00-16:30"

T-3 days: Bedieningsplan finalised
  • Switching plan details: "Open switch Y to isolate zone"
  • Attacker plans: "During this 90-minute window, reprogram RTU in same zone"
  • RTU firmware change takes 20 minutes; work plan covers full 90 minutes
  • Overhead: 70 minutes of documented work + 20 minutes unauthorised

T-1 day: Contractor assigned, access granted
  • Contractor credentials activated in e-terracontrol
  • Physical site access badge enabled
  • Engineering workstation access provisioned


MAINTENANCE WINDOW EXECUTION (day of work)
────────────────────────────────────────────

14:30  | Work team arrives, site security check
       | Legitimate activity: setup, verify de-energisation
       │
14:50  | Authorised switching begins
       | Contractor closes switch Y per bedieningsplan (documented)
       │
14:55  | Supervision focus: switchpoint replacement (main task)
       | ← Window of opportunity: attacker has legitimate reason to access RTU
       │  RTU in same zone needs to be verified de-energised
       │
15:00  | UNAUTHORISED WORK STARTS (hidden in scope)
       | • Attacker connects to RTU with e-terracontrol engineering tool
       | • Loads and modifies RTU firmware
       | • Adds dormant trigger code (dead man's switch)
       | • Firmware upload: takes 15 minutes
       │
15:15  | Authorised work continues (switchpoint replacement)
       | • Main task progresses on schedule
       | • Site supervisor checks on progress
       | • RTU firmware modification complete and unobserved
       │
15:25  | HIDDEN MALICIOUS CONFIGURATION (additional unauthorised work)
       | • Attacker modifies RTU I/O mapping
       | • Changes "Output 1 = close Switchpoint A" → "Output 1 = open Switchpoint B"
       | • Modification time: 5 minutes (hidden in switchpoint replacement activity)
       │
15:35  | Switch Y re-opened per bedieningsplan (closing the maintenance window)
       | • Site returns to normal operational state
       | • Authorised work documented and signed off
       │
16:30  | Team departs, site secured
       | • Unauthorised firmware modification: undetected
       | • Unauthorised I/O mapping: will only manifest when triggered
       | • Work order completion shows: "Switchpoint replaced, RTU verified"
       | • No record that RTU settings were accessed


EVIDENCE TRAIL (what might reveal the abuse)
─────────────────────────────────────────────

If Stedin investigates after unexpected RTU behaviour:

Timestamp mismatch:
  • Work plan: switchpoint replacement 15:00-16:30
  • RTU event log: firmware loaded 15:03-15:18 (outside main task window)
  • Question: why was RTU firmware touched during switchpoint replacement?

Access audit:
  • Engineering workstation log: contractor accessed e-terracontrol 15:03-15:25
  • DIGSI connection log: firmware upload session detected
  • Contractor's claim: "only verified de-energised state"
  • But logs show: firmware read, modify, write operations

Baseline divergence:
  • Before: RTU firmware version v2.1.0, I/O mapping documented
  • After: RTU reports v2.1.0 (attacker preserved version string)
  • But: online-vs-offline comparison flags divergence (attacker failed to update baseline)
  • Or: comparison passes because attacker corrupted baseline too

Device behaviour:
  • Unexpected RTU state reports (false values)
  • Commands execute on wrong switchpoints
  • Autonomous actions trigger (frequency drops to 48.5 Hz, RTU opens unscheduled load)

Hidden changes in authorised work

Authorised maintenance at Stedin often requires configuration changes: updating SIPROTEC or SEL relay settings, modifying e-terracontrol SCADA configuration, or changing Smallworld network model entries. An attacker who is part of the maintenance team could include unauthorised changes in the authorised work.

For instance, a maintenance activity at Stedin might authorise changing a relay’s time delay from 100 milliseconds to 150 milliseconds. The work plan documents this change. During the maintenance, an insider could make that change, but could also change the relay’s threshold from 1200A to 1500A. The threshold change is unauthorised and is not documented, but if the relay settings comparison is done after the maintenance without detailed record-keeping of what changed, the two changes (the authorised and the unauthorised) might go unnoticed together.

More subtly, an insider might document the authorised change correctly but make a different change than documented. The work plan says “change threshold to 1200A” but the insider actually changes it to 1500A. The maintenance paperwork shows the correct change was made (the insider signs the work-order completion in Maximo), but the actual relay has the wrong setting.

This requires the attacker to have technical knowledge of the system and access to the engineering tools (DIGSI 5 for SIPROTEC, AcSELerator QuickSet for SEL, or similar). Contractors who perform Stedin’s protection relay maintenance have this knowledge and access, making them a particular risk.

Unauthorised network access during maintenance

Maintenance windows at Stedin often require granting temporary access to systems that are normally restricted. A contractor might need access to an engineering workstation to load relay settings, or might need physical access to a Stedin substation to replace equipment. An attacker could use a maintenance window as justification for accessing a system, then use that access to plant malicious software or gather information.

For instance, a contractor might request access to a Stedin engineering workstation during a maintenance window to update SIPROTEC or SEL relay firmware. The operator grants access, expecting the contractor to update one relay. The contractor could use this access to install malware on the workstation, to compromise Stedin’s settings database, or to steal a copy of the network model from Smallworld.

Alternately, a contractor with physical access to a Stedin substation could plant test equipment (a device that monitors network traffic, logs relay commands, or injects false frames). The test equipment would be left in the substation after the maintenance window ends, providing persistent access to the network even after the maintenance window closes.

Detecting unauthorised access during maintenance depends on monitoring what the contractor actually does during the window and comparing it against what the work plan authorised. This requires on-site supervision, auditing of system access logs, and physical inspection of equipment after Stedin’s maintenance.

Observable traces

What maintenance window abuse might look like: work orders that don’t match the actual changes made, switching plans that differ from the executed switching, configuration changes outside the scope of the maintenance, unauthorised test equipment connected to the network.

The first evidence is a discrepancy between Stedin’s work plan and the actual work performed. The work plan specifies what will be done; the completion record should document that it was done exactly as planned. If the work-order completion record in IBM Maximo shows changes that are not in the work plan, or if the actual system state after maintenance differs from what the work plan specified, that indicates unauthorised work.

For configuration changes, the as-found-and-as-left records are the critical trace. Before maintenance, the technician documents the current state of the SIPROTEC or SEL relay or e-terracontrol SCADA setting. After maintenance, they document the final state. The comparison should show only the changes documented in the work plan. Additional changes indicate unauthorised modifications.

For switching operations, Stedin’s bedieningsplan specifies what switches will be operated. The operator or technician documents what switches were actually operated in a log or work order. If the actual switches operated differ from the plan, that indicates either a deviation from the plan (which should be approved) or unauthorised switching.

For unauthorised equipment or malware installation, physical inspection after maintenance is the primary detection method. An unexpected device in a substation (a logging device, a repeater, or similar) would be physically visible. Malware installation on a Stedin engineering workstation would be detected through endpoint protection tools or through suspicious system behaviour.

Time records can also reveal abuse. If a maintenance activity is scheduled for four hours but the technician logs many more hours, and there is no documented reason for the longer duration (such as unexpected complications documented in the work order in Maximo), that could indicate additional unauthorised work.

Network-access logs can show whether a contractor accessed systems beyond what the work plan authorised. If Stedin’s work plan authorises access to one relay but the access logs show the contractor connected to five relays, that is a deviation worth investigating.

A pattern of unusual changes across multiple Stedin maintenance windows could indicate systematic abuse. If several maintenance activities result in configuration changes that are outside the work plan, or if costs or resource hours systematically exceed what was estimated, that pattern suggests that the maintenance windows are being used for unauthorised purposes.

The challenge for the defender is that maintenance windows involve legitimate changes and legitimate access to normally-restricted systems, so distinguishing unauthorised work from authorised work requires detailed documentation and careful comparison. An insider who understands the procedures and documentation can hide unauthorised work by carefully documenting it as if it were authorised, or by making small unauthorised changes alongside large authorised changes where they are not immediately noticed.