Communications evidence¶
The portrait’s distribution network communicates via IEC 60870-5-104 telecontrol between the e-terra SCADA and field RTUs, and via CDMA machine-to-machine on Utility Connect’s network for smart-meter collection.
IEC 60870-5-104 protocol structure¶
IEC 60870-5-104 is the primary field-to-control communications protocol: a master-slave design where the SCADA polls RTUs over TCP/IP on port 2404, issuing commands (Close, Open) and reading state. The transport layer carries integrity; the application frame itself is unauthenticated and defines no checksum, which is what makes the traffic worth watching.
Normal IEC 60870-5-104 traffic shows a predictable pattern. The SCADA connects to an RTU, performs a sequence of operations (reading state, issuing commands, reading back new state), and closes the connection. Each message is acknowledged by the RTU. The timing is regular: SCADA connects, sends request, waits for response (usually milliseconds), sends next request. This sequence repeats for each RTU the SCADA manages. Outside of maintenance windows, traffic is lightweight (a few messages per minute per RTU, mostly unsolicited reports from RTUs to SCADA when state changes).
During a maintenance operation (an operator at the control centre executing a planned switching sequence), traffic to a specific RTU increases as operators issue commands and query state. The increase is expected and documented (a bedieningsplan specifies the sequence of commands). The operator’s view of the sequence matches the RTU’s view: commands issued match commands received, in the same order, with the same timing.
Protocol capture and anomaly detection¶
Network captures of IEC 60870-5-104 traffic are the raw forensic source where they exist, and on OT networks they often do not: bandwidth, storage and the age of the kit mean only sampled traffic, or nothing, tends to be kept. Where no capture was running, the pcap-based checks below are unavailable, and the record falls back to the endpoints’ own logs, the very logs a capture would be there to cross-check. Where one does exist, a network analyser or IDS records all traffic between the SCADA and RTUs, stored in pcap format and readable by standard tools like Wireshark, and a pcap file is a complete transcript of what was communicated.
Normal protocol operation shows messages that conform to the IEC 60870-5-104 standard. Each message type can be parsed by a protocol decoder and the payload understood. Command messages have specific structures, response messages match expected types. Replay detection is straightforward: if a command message appears twice in rapid succession (less than a second apart) and the SCADA’s own log shows only one command being issued, the second message in the capture is a replay.
An anomalous capture reads as a non-conformant device or an attack, and the malformed frame is where it starts: a command carrying an invalid type identifier, a response of no valid type, an address outside the range the estate uses. The sharper tell is a mismatch of question and answer, the SCADA issuing Close A and the RTU acknowledging B closed, which is command injection or a badly misconfigured RTU.
Timing shows too. A command and its answer normally sit 10 to 500 milliseconds apart; a gap stretched to five or ten seconds is congestion or an RTU labouring under something, and a burst of commands fired off without waiting for a reply, three inside ten milliseconds, is either pipelining the protocol allows or an attacker running commands on a script.
Network topology and unexpected connections¶
The distribution network topology is well-defined: the e-terra SCADA is in the control centre, RTUs are in substations scattered across the region, and communication flows between them over dedicated network links or VPN tunnels. Unexpected connections to RTUs (a connection from an engineering workstation that is not the authorised engineering tool, or a connection from outside the network) are anomalies.
Authorised connections include: the main SCADA (initiating connections to all RTUs regularly), authorised engineering workstations (connecting to RTUs during maintenance windows), and backup systems (standby SCADA or engineering tools configured as redundancy). Any connection outside this list does not fit the baseline. A connection from an arbitrary IP address to an RTU’s IEC 60870-5-104 port (2404) is a red flag. If the firewall logs show such a connection, and no staff authorised it, it is evidence of either a network intrusion or a serious misconfiguration.
The control-centre network is segmented from corporate IT for security. An RTU in a substation is directly connected to the control centre’s OT network, or connected via an encrypted VPN tunnel if it is remote. A connection from an external network (the public internet, a contractor’s network) directly to an RTU would require bypassing the network perimeter, which would be detected by firewall logs. If such a connection appears in the logs with no corresponding firewall alert, either the firewall logs were not complete or the connection was made through a compromised path (a device inside the network acting as a relay).
Metering communications and CDMA patterns¶
Smart meters communicate with the Utility Connect CDMA network to report consumption. Meters (Landis+Gyr, Iskraemeco, Kaifa, Sagemcom) periodically transmit their readings to data concentrators that relay the data to the metering platform. The normal pattern is a high-frequency burst of meter readings coming into the platform during the metering windows (once or twice daily when meters report).
A baseline for metering traffic is the expected number of meters reporting during each collection window, the typical consumption values, and the distribution of readings across the customer base. Anomalies in metering traffic include: a sudden drop in the number of meters reporting (half of the meters in a feeder suddenly go silent), sudden spikes in consumption readings (a feeder that normally shows 100 kW suddenly shows 1000 kW), consumption data that is suspiciously round (all meters reporting exactly 1000 Wh with no variation), or missing periods (the metering data collection for an entire hour is missing).
Metering data can be tampered with at three points, and each leaves a different mark. At the meter, one device reports a value that a technician’s own reading of its display contradicts. In transmission, a whole CDMA concentrator’s worth of meters go wrong together, because the interception hits them as a group. At the platform, the stored figures drift while the meters themselves stay honest, so only the database and its audit trail carry the change.
CDMA network logs and transmission patterns¶
Utility Connect operates the CDMA machine-to-machine network. The CDMA network maintains logs of which meters transmitted, when, and what data was received. For forensic analysis, access to Utility Connect’s logs (if permitted) provides an independent view of metering traffic. If the metering platform shows meter XYZ reported 500 Wh at 15:00 UTC, Utility Connect’s logs show the meter transmitted that data at approximately the same time.
A divergence between the platform record and Utility Connect’s network log indicates tampering at either layer. If the platform shows a meter reported 500 Wh but Utility Connect’s log shows the meter transmitted 450 Wh, the platform data was edited after reception. If Utility Connect shows transmission at 15:00 UTC but the platform records the same transmission at 15:15 UTC, there is a time-synchronisation issue or the data was held and inserted later.
Normal CDMA transmission patterns are regular and repeating. Meters transmit during defined windows (often early morning or late evening), the transmission latency is consistent (seconds to minutes from meter transmission to platform receipt), and the volume is stable (the same percentage of meters report each cycle). Anomalies include transmission windows that shift (meters reporting at unusual times), increased latency (data arriving hours late), or missing transmissions (transmission windows with no data arriving).
IDS and anomaly detection¶
The network infrastructure (firewalls, network switches, and potentially intrusion-detection systems) logs connections, traffic volume, and protocol anomalies. If an IDS is deployed on the OT network, it would detect suspicious patterns: port scans, protocol violations, unusual traffic volumes, or traffic to unexpected destinations.
An IDS watching IEC 60870-5-104 traffic would flag messages that do not conform to the protocol standard, unusual command sequences, or high-frequency commands that exceed normal baselines. Modern IDS systems can be trained on baseline normal traffic and then flag deviations. If the IDS shows a surge in IEC 60870-5-104 commands to a specific RTU, with the commands coming from an unexpected source, that is evidence of anomalous activity.
The limitation of IDS alerts is that they can generate false positives. A legitimate but unusual command sequence ( perhaps a technician manually testing an RTU with a sequence that rarely occurs) might trigger an IDS alert without being malicious. IDS alerts provide initial pointers for investigation, and need reading against operational activity and work orders before they mean much.
Traffic volume and timing baselines¶
Beyond protocol-level analysis, traffic volume and timing provide forensic clues. The SCADA maintains a predictable communication pattern: regular polling of all RTUs on a cycle (perhaps every minute), occasional commands during operational windows, and unsolicited reports when RTU state changes. The total traffic volume per hour is relatively stable: thousands of IEC 60870-5-104 messages per hour, but the rate is consistent.
A sudden spike in traffic volume stands out. If the average traffic is 5000 messages per hour but a specific hour shows 50,000 messages, something unusual happened. The spike could be a legitimate operational activity (an extended switching operation requiring hundreds of manual commands) or it could be an attack (an attacker issuing commands automatically). Distinguishing them requires examining the messages themselves to see if they correspond to documented work or not.
Timing baselines are also observable. If the network normally exchanges IEC 60870-5-104 traffic during working hours (08:00-18:00) with minimal traffic at night, a sudden burst of traffic at 03:00 is anomalous. Again, this could be explained by legitimate out-of-hours emergency work (a fault requiring urgent response) or it could be an attack. The explanation depends on whether an emergency was documented and whether the traffic pattern matches the expected emergency response.
The SCADA polls on a steady cycle, thousands of messages an hour, so the traffic is heavy and an intrusion shows less in the volume than in the shape. One Close command on the wire, three ways it arrives:
A CLOSE COMMAND IN THE 104 CAPTURE
──────────────────────────────────
LEGITIMATE │ REPLAY │ INJECTION
SCADA own log one match │ logged once │ no matching command
count on wire one │ two in <1 s │ one
RTU response "A Closed" │ "A Closed" │ "B Closed" to "Close A"
source the main SCADA │ the main SCADA │ an arbitrary IP to :2404